1、 Product overview
Lj8c1-hd intelligent harmonic suppression reactive compensation unit is a new generation reactive power compensation equipment developed by our company to improve power factor, instead of the traditional reactive compensation equipment composed of fuse, switch on and off, filter reactor and power capacitor; it is mainly used in reactive compensation in very serious harmonic occasions, which can operate reliably without resonance and harmonic reactive power The amplification function is that there are 4.5% or 6%, 7%, 12% and 13% filter reactors in the circuit circuit, which can effectively absorb the harmonic current of 3, 5, 7 times and above, improve the power quality and stabilize the power grid.

For good heat dissipation, the horizontal spacing between modules shall not be less than 50 mm, and the vertical spacing shall leave room for operating the screw driver. Generally speaking, the cabinet with a width of 1200mm * a depth of 800mm * a height of 2200mm can be installed in two layers, and each layer can be installed with 6 sets, a total of 12 sets, up to 480kvar.